Performance Specification Model: IAQ-4000-RT-BP-HW Supply cfm: 3,000 Exhaust cfm: 3,000 Built: February, 2007 Dimensions: 39" H, 144" L, 68" W Weight: 3,000 lbs Energy: 139 MBH (Winter) Recovered: 41 MBH (Summer) Design: 4 °F / 45% RH (Winter) Conditions: 95 °F / 40% RH (Summer)
|
|
|
View 1 |
||
|
|
||
|
View 2 |
||
|
Unit Features |
||
|
● XLT-40-24 Aluminum, Flat Plate Heat Exchanger ● 280 MBH Hot Water Coil ● 12" Heavy Duty, Forward Curved, DWDI Blowers driven by Premium Efficiency Motors (3hp supply / 2hp exhaust) mounted on RIS Isolators ● 4” 30/30 Outside Air and Return Air Filters ● Outside and Exhaust Air Shut- Off, Face and Bypass, and Recirculation Dampers ● Heavy Duty Double Wall with Enamel Painted Galvanized Steel Exterior (16 ga) and Galvanized Steel Interior (22 ga); 2" Thick Fiberglass Insulated; All Welded Structural Steel Base Frame with Integral Lifting Lugs ● Galvanized Steel Drain Pan ● Frost Control and Warm Weather Economizer ● Configured for Outdoor, Rooftop installation with 18" Roof Curb, Slopped Cabinet Roof with Capped Seams, and Intake and Exhaust Hoods ● Complete with Motor Starters and Breakers; Disconnect; and Single Point Power Connection |
||